ACU2-60-5-2-E3000电流互感器
        添加时间:2010-10-16  编辑:X059  阅读:次
	
	
        
        
        
        
          
            - 产品名称:ACU2-60-5-2-E3000电流互感器
- 产品定货号:ME-06635-00
 
        
       
      
        6" Diameter Current Transformer5A base Intelligent Power Meter
Metering of distribution feeders, transformers, generators, capacitor banks and motors 
Medium and low voltage systems 
Commercial, industrial, utility 
Power quality analysis 
Web Server and Email Sending 
Over Limit Alarm 
Remote Switch Controlling 
Switch Status Monitoring 
UL & CE Certified
| The Accuenergy Acuvim II is a high-end multifunction power meter manufactured by Accuenergy. It is the ideal choice for monitoring and controlling of power distribution systems. Some of the features and electric power parameters available on the ultra-compact Acuvim II are: | 
| True-RMS Measuring Parameter  4-Quadrant Energy  Power Quality Analysis  Over Limit Alarm  Multi Communication Ports (Eg: Ethernet, Modbus)  Web Server and Email Sending  Switch Status Monitoring  Remote Switch Controlling  Module Design (E-Module® Technique) | 
| Accuenergy Acuvim-2 may be used as a data gathering device for an intelligent Power Distribution System or Plant Automation System. All monitored data is available via a digital RS485 communication port running Modbus™ Protocol. Ethernet and Profibus DP communication are also options and with new wireless technologies and protocols currently under development, the applications for the Accuenergy Acuvim-II meter are limitless. | 
|   | 
| Specifications | 
| Parameters | Accuracy | Resolution | Range | 
| Voltage | 0.2% | 0.1V | 20V ~ 500kV | 
| Current | 0.2% | 0.001A | 5mA ~ 50000A | 
| Power | 0.5% | 1W | -9999MW ~ 9999MW | 
| Reactive Power | 0.5% | 1 Var | -9999MVar ~ 9999MVar | 
| Apparent Power | 0.5% | 1VA | -9999 ~ 9999MVA | 
| Power Demand | 0.5% | 1W | -9999MW ~ 9999MW | 
| Reactive Power Demand | 0.5% | 1Var | -9999MVar ~ 9999MVar | 
| Apparent Power Demand | 0.5% | 1VA | -9999MVA ~ 9999MVA | 
| Power Factor | 0.5% | 0.001 | -1.000 ~ 1.000 | 
| Frequency | 0.2% | 0.01Hz | 45.00 ~ 65.00Hz | 
| Energy | Primary | 0.5% | 0.1kQh | 0 - 99,999,999.9kWh | 
| Secondary | 0.5% | 0.001kWh | 0 - 99,99.999kWh | 
| Reactive Energy | Primary | 0.5% | 0.1kvarh | 0 - 99,999,999.9kVarh | 
| Secondary | 0.5% | 0.001kvarh | 0 - 999,999.999kVarh | 
| Apparently Energy | Primary | 0.5% | 0.1kVAh | 0 - 99,999,999.9kVAh | 
| Secondary | 0.5% | 0.001kVAh | 0 - 999,999.999kVAh | 
| Harmonics | 2.0% | 0.1% | 0.0% ~ 100.0% | 
| Phase Angle | 2.0% | 0.1° | 0.0° ~ 359.9° | 
| Imbalance Factor | 2.0% | 0.1% | 0.0% ~ 100.0% | 
| Running Time |   | 0.01h | 0 ~ 9,999,999.99h |